Strona 1 - Installation Manual

Protect PV - Solar InvertersInstallation ManualAEG Power Solutions GmbHRevision: 01Date: 2011-05-25Installation Manual8000038781_00_BAL_en

Strona 2 - Contents

Illustration 3.1: Safe DistancesObserve these distances when installing one or more inverters. One row mounting is recom-mended. Contact the

Strona 3 - 1. Safety and Conformity

3.2. Mounting the InverterFor the safe handling of the inverter, two people must carry the unit, or a suitabletransport trolley must be used. Safety b

Strona 4 - PV Load Switch

Illustration 3.5: Place Inverter in MountingBracketPlace the lower part of the inverter againstthe mounting bracket.Illustration 3.6: Fast

Strona 5 - 1.4. Conformity

Removal is performed in the reverse order of mounting. With a firm grip at the lower end of theinverter, lift the inverter approximately 20 mm vertica

Strona 6 - 2. Introduction

Illustration 3.8: Open the InverterPush the front cover upwards. When a slightresistance is felt, give the front cover a tapon the bottom t

Strona 7 - 2.1.1. Installation Sequence

Illustration 3.10: Fasten Front Screws and En-sure Proper PE Connection.The two front screws are the PE connection to the front cover

Strona 8 - 2.1.2. Overview of Inverter

Illustration 3.11: AC Cable Wire StripLegend1 Blue cable - Neutral2 Yellow/green cable - EarthThe illustration shows the stripping of insulation of al

Strona 9

6. The Protective Earth wire (PE) is mandatory and must be connected directly to thechassis PE terminal. Insert the wire and fasten the s

Strona 10 - 3. Installation

When unmated the MC4 connectors are not IP54. The intrusion of moisture mayoccur in the following situations:1. The inverter runs in Master/Slave op

Strona 11 - 3.2. Mounting the Inverter

4. Start-up and Check of Settings4.1. Start-up and Check of SettingsNote: Due to the advanced functionalities of the inverter, it may take up to 10 se

Strona 12 - 3.3. Removing the Inverter

Contents1. Safety and Conformity2Safety Information 2Hazards of PV Systems 3PV Load Switch 3Conformity 4Approvals and Certifications 42. Introduction5

Strona 13

Illustration 4.2: Set TimeSet time as prompted by the display. Press'OK' to select number. Press ‘ ▲ ’ to scroll upthrough the numb

Strona 14 - 3. Installation

Illustration 4.4: Installed PV PowerEnter the amount of installed PV power foreach of the PV inputs. When two or more PVinputs are connected in

Strona 15 - 3.5. AC Grid Connection

Note: If the two country selections do not match they will be cancelled and it will be necessary toredo the selections. If a wrong country is accident

Strona 16

of larger networks. Replication can be performed once, prior to defining the country setting infollower inverters.Illustration 4.7: Master ModeTo ena

Strona 17 - 3.6. PV Connection

5. Technical Data5.1. Technical DataNomen-cla-ture 1)ParameterProtect PV10 kWProtect PV12.5 kWProtect PV15 kW AC Pac,rMax./Nom. power AC 10000 W

Strona 18 - Auxiliary Input/Output

1) According to FprEN 50524.2) For fixed systems with semi-optimal conditions.3) At identical input voltages. At unequal input voltages, Vmppmin can b

Strona 19

Parameter SpecificationTemperature -25°C - +60°C (>45°C derating)Environmental class according to IEC IEC60721-3-33K6/3B3/3S3/3M2Air quality ISA S7

Strona 20 - Illustration 4.3: Set Date

Illustration 5.1: Protect PV 10 kW Cable Losses [%] versus Cable Length [m]Illustration 5.2: Protect PV 12.5 kW Cable Losses [%] versus Cable Length [

Strona 21

- Layout type (inside wall, under ground, free air etc.)- UV resistanceIllustration 5.4: Overview of Inverter with Torque IndicationsParameterScrewdri

Strona 22 - Master Mode

5.1.2. Wiring DiagramIllustration 5.5: Typical Installation5. Technical Data 28 8000038781_00_BAL_en / L00410564-01_02 5

Strona 23 - Inverter

1. Safety and Conformity1.1. Safety InformationAll persons installing and servicing inverters must be:• Trained and experienced in general safety rule

Strona 24 - 5. Technical Data

5.1.3. Auxiliary Interface SpecificationsParameter Parameter details SpecificationSerial Communication RS485Common cable specificationCable jacket d

Strona 25

1) Max. number of inverters are 100. If GSM modem is used for portal upload, the amount of inverters in anetwork is limited to 50.2) For outdoor use,

Strona 26 - 5.1.1. Cable Requirements

5.1.4. RS485 Communication Board ConnectionsIllustration 5.7: RS485 Detail of Communication Board.BIAS L and Bias H are to be connected to RX/TX B and

Strona 27

Lit. No. L00410564-01_02 Rev. date 2011-05-25France & AfricaAEG Power SolutionsZI 10 rue Jean Perrin37173 Chambray-lès-ToursTel: + 332 47 80 88

Strona 28

Before installation:Check for damage to inverter and packaging. If in doubt, contact the supplier be-fore installing the inverter.Installation:For opt

Strona 29 - 5.1.2. Wiring Diagram

1.4. Conformity1.4.1. Approvals and CertificationsFor more information, go to the download area at www.aegps.com/solarinverters, Approvalsan

Strona 30

2. Introduction2.1. IntroductionThis manual explains the installation and setup of the Protect PV solar inverter, for the installa-tion technician.Ill

Strona 31

Protect PVvariantUser interface Ancillary services DC power rat-ing Local Web Server Power Level Adjust-ment,Primary FrequencyControlRide Through Fau

Strona 32

2.1.2. Overview of InverterIllustration 2.3: Overview of AEG PS Protect PV inverterLive Part1. AC Connection Area2. DC Connection Area3. Terminal bloc

Strona 33

3. Installation3.1. Installation Dimensions and PatternsNote: When choosing the installation place, ensure that all labels are visible at all times.Fo